Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
674
2898 No. of higher AR-cycle CLOSE
commands,3p (79 #Close2./3p=)
Statistics VI
2899 79: Close request to Control
Function (79 CloseRequest)
79M Auto Recl. OUT * on * LED BO
4601 >52-a contact (OPEN, if bkr is
open) (>52-a)
P.System Data 2 SP On
Off
**LEDBIBO
4602 >52-b contact (OPEN, if bkr is
closed) (>52-b)
P.System Data 2 SP On
Off
**LEDBIBO
4822 >BLOCK Motor Startup counter
(>BLOCK 66)
48/66 Motorprot SP * * * LED BI BO
4823 >Emergency start (>66 em-
er.start)
48/66 Motorprot SP On
Off
* * LED BI BO 168 51 1 Yes
4824 66 Motor start protection OFF (66
OFF)
48/66 Motorprot OUT On
Off
* * LED BO 168 52 1 Yes
4825 66 Motor start protection
BLOCKED (66 BLOCKED)
48/66 Motorprot OUT On
Off
On
Off
* LED BO 168 53 1 Yes
4826 66 Motor start protection ACTIVE
(66 ACTIVE)
48/66 Motorprot OUT On
Off
* * LED BO 168 54 1 Yes
4827 66 Motor start protection TRIP
(66 TRIP)
48/66 Motorprot OUT On
Off
* * LED BO 168 55 1 Yes
4828 >66 Reset thermal memory (>66
RM th.repl.)
48/66 Motorprot SP On
Off
**LEDBIBO
4829 66 Reset thermal memory (66
RM th.repl.)
48/66 Motorprot OUT On
Off
**LEDBO
4834 66 Rotor overload TRIP (66
OVERL. TRIP)
48/66 Motorprot OUT on on * LED BO
4835 66 Rotor Overload Alarm (66
OVERL.ALARM)
48/66 Motorprot OUT On
Off
**LEDBO
5143 >BLOCK 46 (>BLOCK 46) 46 Negative Seq SP * * * LED BI BO 70 126 1 Yes
5145 >Reverse Phase Rotation (>Re-
verse Rot.)
P.System Data 1 SP On
Off
**LEDBIBO
5147 Phase rotation ABC (Rotation
ABC)
P.System Data 1 OUT On
Off
* * LED BO 70 128 1 Yes
5148 Phase rotation ACB (Rotation
ACB)
P.System Data 1 OUT On
Off
* * LED BO 70 129 1 Yes
5151 46 switched OFF (46 OFF) 46 Negative Seq OUT On
Off
* * LED BO 70 131 1 Yes
5152 46 is BLOCKED (46 BLOCKED) 46 Negative Seq OUT On
Off
On
Off
* LED BO 70 132 1 Yes
5153 46 is ACTIVE (46 ACTIVE) 46 Negative Seq OUT On
Off
* * LED BO 70 133 1 Yes
5159 46-2 picked up (46-2 picked up) 46 Negative Seq OUT * On
Off
* LED BO 70 138 2 Yes
5165 46-1 picked up (46-1 picked up) 46 Negative Seq OUT * On
Off
* LED BO 70 150 2 Yes
5166 46-TOC picked up (46-TOC
pickedup)
46 Negative Seq OUT * On
Off
* LED BO 70 141 2 Yes
5170
46 TRIP (46 TRIP) 46 Negative Seq OUT * on m LED BO 70 149 2 Yes
5171 46 Disk emulation picked up (46
Dsk pickedup)
46 Negative Seq OUT * * * LED BO
5203 >BLOCK 81O/U (>BLOCK
81O/U)
81 O/U Freq. SP On
Off
* * LED BI BO 70 176 1 Yes
5206 >BLOCK 81-1 (>BLOCK 81-1) 81 O/U Freq. SP On
Off
* * LED BI BO 70 177 1 Yes
5207 >BLOCK 81-2 (>BLOCK 81-2) 81 O/U Freq. SP On
Off
* * LED BI BO 70 178 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation