Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
675
5208 >BLOCK 81-3 (>BLOCK 81-3) 81 O/U Freq. SP On
Off
* * LED BI BO 70 179 1 Yes
5209 >BLOCK 81-4 (>BLOCK 81-4) 81 O/U Freq. SP On
Off
* * LED BI BO 70 180 1 Yes
5211 81 OFF (81 OFF) 81 O/U Freq. OUT On
Off
* * LED BO 70 181 1 Yes
5212 81 BLOCKED (81 BLOCKED) 81 O/U Freq. OUT On
Off
On
Off
* LED BO 70 182 1 Yes
5213 81 ACTIVE (81 ACTIVE) 81 O/U Freq. OUT On
Off
* * LED BO 70 183 1 Yes
5214 81 Under Voltage Block (81
Under V Blk)
81 O/U Freq. OUT On
Off
On
Off
* LED BO 70 184 1 Yes
5232 81-1 picked up (81-1 picked up) 81 O/U Freq. OUT * On
Off
* LED BO 70 230 2 Yes
5233 81-2 picked up (81-2 picked up) 81 O/U Freq. OUT * On
Off
* LED BO 70 231 2 Yes
5234 81-3 picked up (81-3 picked up) 81 O/U Freq. OUT * On
Off
* LED BO 70 232 2 Yes
5235 81-4 picked up (81-4 picked up) 81 O/U Freq. OUT * On
Off
* LED BO 70 233 2 Yes
5236 81-1 TRIP (81-1 TRIP) 81 O/U Freq. OUT * on m LED BO 70 234 2 Yes
5237 81-2 TRIP (81-2 TRIP) 81 O/U Freq. OUT * on m LED BO 70 235 2 Yes
5238 81-3 TRIP (81-3 TRIP) 81 O/U Freq. OUT * on m LED BO 70 236 2 Yes
5239 81-4 TRIP (81-4 TRIP) 81 O/U Freq. OUT * on m LED BO 70 237 2 Yes
5951 >BLOCK 50 1Ph (>BLK 50 1Ph) 50 1Ph SP * * * LED BI BO
5952 >BLOCK 50 1Ph-1 (>BLK 50
1Ph-1)
50 1Ph SP * * * LED BI BO
5953 >BLOCK 50 1Ph-2 (>BLK 50
1Ph-2)
50 1Ph SP * * * LED BI BO
5961 50 1Ph is OFF (50 1Ph OFF) 50 1Ph OUT On
Off
**LEDBO
5962 50 1Ph is BLOCKED (50 1Ph
BLOCKED)
50 1Ph OUT On
Off
On
Off
* LED BO
5963 50 1Ph is ACTIVE (50 1Ph
ACTIVE)
50 1Ph OUT On
Off
**LEDBO
5966 50 1Ph-1 is BLOCKED (50 1Ph-1
BLK)
50 1Ph OUT On
Off
On
Off
* LED BO
5967 50 1Ph-2 is BLOCKED (50 1Ph-2
BLK)
50 1Ph OUT On
Off
On
Off
* LED BO
5971 50 1Ph picked up (50 1Ph
Pickup)
50 1Ph OUT * On
Off
* LED BO
5972 50 1Ph TRIP (50 1Ph TRIP) 50 1Ph OUT * on * LED BO
5974 50 1Ph-1 picked up (50 1Ph-1
PU)
50 1Ph OUT * On
Off
* LED BO
5975 50 1Ph-1 TRIP (50 1Ph-1 TRIP) 50 1Ph OUT * on * LED BO
5977 50 1Ph-2 picked up (50 1Ph-2
PU)
50 1Ph OUT * On
Off
* LED BO
5979 50 1Ph-2 TRIP (50 1Ph-2 TRIP) 50 1Ph OUT * on * LED BO
5980 50 1Ph: I at pick up (50 1Ph I:) 50 1Ph VI * On
Off
6503 >BLOCK 27 undervoltage pro-
tection (>BLOCK 27)
27/59 O/U Volt. SP * * * LED BI BO 74 3 1 Yes
6505 >27-Switch current supervision
ON (>27 I SUPRVSN)
27/59 O/U Volt. SP On
Off
* * LED BI BO 74 5 1 Yes
No. Description Function Type
of
In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com