Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
676
6506 >BLOCK 27-1 Undervoltage pro-
tection (>BLOCK 27-1)
27/59 O/U Volt. SP On
Off
**LEDBIBO7461Yes
6508 >BLOCK 27-2 Undervoltage pro-
tection (>BLOCK 27-2)
27/59 O/U Volt. SP On
Off
**LEDBIBO7481Yes
6509 >Failure: Feeder VT
(>FAIL:FEEDER VT)
Measurem.Superv SP On
Off
**LEDBIBO7491Yes
6510 >Failure: Busbar VT (>FAIL: BUS
VT)
Measurem.Superv SP On
Off
**LEDBIBO74101Yes
6513 >BLOCK 59 overvoltage protec-
tion (>BLOCK 59)
27/59 O/U Volt. SP * * * LED BI BO 74 13 1 Yes
6530 27 Undervoltage protection
switched OFF (27 OFF)
27/59 O/U Volt. OUT On
Off
**LEDBO74301Yes
6531 27 Undervoltage protection is
BLOCKED (27 BLOCKED)
27/59 O/U Volt. OUT On
Off
On
Off
* LED BO 74 31 1 Yes
6532 27 Undervoltage protection is
ACTIVE (27 ACTIVE)
27/59 O/U Volt. OUT On
Off
**LEDBO74321Yes
6533 27-1 Undervoltage picked up
(27-1 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 33 2 Yes
6534 27-1 Undervoltage PICKUP
w/curr. superv (27-1 PU CS)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 34 2 Yes
6537 27-2 Undervoltage picked up
(27-2 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 37 2 Yes
6538 27-2 Undervoltage PICKUP
w/curr. superv (27-2 PU CS)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 38 2 Yes
6539 27-1 Undervoltage TRIP (27-1
TRIP)
27/59 O/U Volt. OUT * on m LED BO 74 39 2 Yes
6540 27-2 Undervoltage TRIP (27-2
TRIP)
27/59 O/U Volt. OUT * on * LED BO 74 40 2 Yes
6565 59-Overvoltage protection
switched OFF (59 OFF)
27/59 O/U Volt. OUT On
Off
**LEDBO74651Yes
6566 59-Overvoltage protection is
BLOCKED (59 BLOCKED)
27/59 O/U Volt. OUT On
Off
On
Off
* LED BO 74 66 1 Yes
6567 59-Overvoltage protection is
ACTIVE (59 ACTIVE)
27/59 O/U Volt. OUT On
Off
**LEDBO74671Yes
6568 59 picked up (59-1 picked up) 27/59 O/U Volt. OUT * On
Off
* LED BO 74 68 2 Yes
6570 59 TRIP (59-1 TRIP) 27/59 O/U Volt. OUT * on m LED BO 74 70 2 Yes
6571 59-2 Overvoltage V>> picked up
(59-2 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO
6573 59-2 Overvoltage V>> TRIP (59-2
TRIP)
27/59 O/U Volt. OUT * on * LED BO
6801 >BLOCK Startup Supervision
(>BLK START-SUP)
48/66 Motorprot SP * * * LED BI BO
6805 >Rotor locked (>Rotor locked) 48/66 Motorprot SP * * * LED BI BO
6811 Startup supervision OFF
(START-SUP OFF)
48/66 Motorprot OUT On
Of
f
* * LED BO 169 51 1 Yes
6812 Startup supervision is BLOCKED
(START-SUP BLK)
48/66 Motorprot OUT On
Off
On
Off
* LED BO 169 52 1 Yes
6813 Startup supervision is ACTIVE
(START-SUP ACT)
48/66 Motorprot OUT On
Off
* * LED BO 169 53 1 Yes
6821 Startup supervision TRIP
(START-SUP TRIP)
48/66 Motorprot OUT * on m LED BO 169 54 2 Yes
6822 Rotor locked (Rotor locked) 48/66 Motorprot OUT * on * LED BO 169 55 2 Yes
6823 Startup supervision Pickup
(START-SUP pu)
48/66 Motorprot OUT On
Off
* * LED BO 169 56 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation