Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
102 Manual, 05/2019, A5E45131885002A/RS-AA/001
Object
No.
Byte Bit Data
format
Parameters Range of values
[encoding]
Incre-
ment
3RW55
1)
[D
2)
]
129 441 0 Bit4 Response to preset unequal
actual configuration of HMI
[0 ... 4] - r/w
[0]
[0] Turn off
[1] Warn
[4] Ignore
2344 443 0 Bit4 Pump cleaning mode [0 ... 1] - r/w
[0]
[0] Deactivated
[1] Manual
2345 444 0 Bit4 Pump cleaning - start/stop
parameters
[1 ... 5] - r/w
[5]
[1] Parameter set 1
[2] Parameter set 2
[3] Parameter set 3
[5] Operating parameters
2346 445 0 USINT Pump cleaning - time 0 ... 30 s
[0 ... 30]
1 s r/w
[20]
2347 446 0 USINT Pump cleaning - cycles 0 ... 10
[0 ... 10]
1 r/w
[3]
2352 447 0 UINT Current limiting value -
maximum
125 ... 800 %
[125 ... 800]
1 % r/w
[400]
2002 457 0 UINT Measured value 1 [20 000 ... 20 006] - r/w
[20 000]
[20 000] Phase current I L1 (rms)
[20 001] Phase current I L2 (rms)
[20 002] Phase current I L3 (rms)
[20 003] Phase current average (rms)
[20 004] Active energy import (total)
[20 005] Active power
[20 006] Power factor L1..3
2003 459 0 UINT Measured value 2 (see Measured value 1) - r/w
[20 001]
2004 461 0 UINT Measured value 3 (see Measured value 1) - r/w
[20 002]
1)
Supported by SIRIUS 3RW55 soft starter
2)
Default encoding
3)
Parameter is relevant for EX applications
4)
From 3RW55 V2.0
Dependencies
During parameterization, it is possible to select impossible combinations of interdependent
values. The "Invalid parameter value" diagnosis is then reported in the Dataset Object "Soft
Starter Diagnostics" (Page 84). You will find the dependencies of the parameters in the
Equipment Manual of the 3RW5 soft starter.