Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
101
Object
No.
Byte Bit Data
format
Parameters Range of values
[encoding]
Incre-
ment
3RW55
1)
[D
2)
]
35 431 0 Bit32 Substitute value - - r/w
[0]
431 0 BOOL Substitute value: Motor CW [0 ... 1] - r/w
[0]
1 BOOL Substitute value: Motor CCW [0 ... 1] - r/w
[0]
3 BOOL Substitute value: Reset [0 ... 1] - r/w
[0]
4 BOOL Substitute value: Emergency
start
[0 ... 1] - r/w
[0]
6 BOOL Substitute value: Creep speed [0 ... 1] - r/w
[0]
432 0 BOOL Substitute value: Output 1 [0 ... 1] - r/w
[0]
1 BOOL Substitute value: Output 2 [0 ... 1] - r/w
[0]
2 BOOL Substitute value: Parameter
set bit 0
[0 ... 1] - r/w
[0]
3 BOOL Substitute value: Parameter
set bit 1
[0 ... 1] - r/w
[0]
7 BOOL Substitute value: Disable
quick-stop
[0 ... 1] - r/w
[0]
433 0 BOOL Substitute value: Output 3 [0 ... 1] - r/w
[0]
3 BOOL Substitute value: Pump
cleaning
[0 ... 1] - r/w
[0]
434 0 BOOL Substitute value: Manual
operation local - input
controlled
[0 ... 1] - r/w
[0]
1 BOOL Substitute value: Use
alternative stopping mode
[0 ... 1] - r/w
[0]
2 BOOL Substitute value: Motor
standstill
[0 ... 1] - r/w
[0]
2310 435 0 Bit4 Parameters of CPU/master
disabled
[1 ... 2] - r/w
[1]
[1] Deactivate
[2] Activate
140 437 0 Bit2 Response to overload
switching element
[0 ... 1] - r/w
[0]
[0] Turn off without restart
[1] Turn off with restart
232 439 0 Bit4 Response to faulty main
power
[1 ... 2] - r/w
[1]
[1] Group error only at ON command
[2] Warn