Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
100 Manual, 05/2019, A5E45131885002A/RS-AA/001
Object
No.
Byte Bit Data
format
Parameters Range of values
[encoding]
Incre-
ment
3RW55
1)
[D
2)
]
2336 413 0 UINT Output 4 - OFF delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
2222 415 0 USINT Analog output - signal type [0 ... 3] - r/w
[0]
[0] Deactivated
[2] 4-20mA
[3] 0-10V
2223 417 0 UINT Analog output - measured
value
[0 ... 632] - r/w
[0]
[0] Deactivated
[502] Motor temperature rise
[504] Phase current I L1 (%)
[505] Phase current I L2 (%)
[506] Phase current I L3 (%)
[510] Line-to-line voltage
U L1-L2 (rms)
[511] Line-to-line voltage
U L2-L3 (rms)
[512] Line-to-line voltage
U L3-L1 (rms)
[513] Phase current I L1 (rms)
[514] Phase current I L2 (rms)
[515] Phase current I L3 (rms)
[518] Switching element heating
[521] Active power
[523] Power factor L1..3
[528] Phase current average (%)
[530] Phase current average (rms)
[632] Active energy import (total)
2224 419 0 UDINT Analog output - range start
value
0 … 4 294 967 295
[0 … 4 294 967 295]
1 r/w
[0]
2225 423 0 UDINT Analog output - range end
value
0 … 4 294 967 295
[0 … 4 294 967 295]
1 r/w
[27 648]
2209 427 0 Bit4 EX application
4)
[0 ... 3] - r/w
3)
[0]
[0] No
[1] Yes, with complete motor
protection
[2] Yes, with thermal motor model
[3] Yes, with PTC temperature
protection
34 429 0 BOOL Response to CPU/Master
Stop
[0 ... 1] - r/w
[0]
[0] Switch substitute value
[1] Keep last value

Table of Contents