Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
99
Object
No.
Byte Bit Data
format
Parameters Range of values
[encoding]
Incre-
ment
3RW55
1)
[D
2)
]
163 397 0 USINT Output 1-Action [0 ... 201] - r/w
[13]
[0] No action
[1] Control source PIQ-DQ-1.0
output 1
[2] Control source PIQ-DQ-1.1
output 2
[6] Control source input 1
[7] Control source input 2
[8] Control source input 3
[9] Control source input 4
[10] Start-up
[11] Operation / bypass
[12] Run-down
[13] On time motor (RUN)
[14] Control command MOTOR ON
[16] DC braking contactor
[18] Device on
[19] Operation / Run-down
[29] External bypass
4)
[31] Group warning
[32] Group error
[33] Bus error
[34] Device error
[38] Ready to start for motor ON
[41] Generator operation
[42] Pump cleaning active
[43] Alternative stopping mode active
[44] CM - maintenance demanded
[45] CM - error
[180] Control source PIQ-DQ 2.0
output 3
[200] Reversing switching element -
right
[201] Reversing switching element -
left
159 399 0 UINT Output 1 - ON delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
2333 401 0 UINT Output 1 - OFF delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
164 403 0 USINT Output 2-Action (see Output 1-Action) - r/w
[0]
160 405 0 UINT Output 2 - ON delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
2334 407 0 UINT Output 2 - OFF delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
166 409 0 USINT Output 4-Action (see Output 1-Action) - r/w
[0]
162 411 0 UINT Output 4 - ON delay time 0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]