EasyManua.ls Logo

Siemens SIRIUS 3RW5 - Page 98

Siemens SIRIUS 3RW5
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
98 Manual, 05/2019, A5E45131885002A/RS-AA/001
Object
No.
Byte Bit Data
format
Parameters Range of values
[encoding]
Incre-
ment
3RW55
1)
[D
2)
]
2220 381 0 USINT Ground fault limit warning 10 … 95 %
[2 … 19]
5 % r/w
[0]
[0] Deactivated
2294 383 0 USINT Ground fault limit error 10 … 95 %
[2 … 19]
5 % r/w
[4]
[0] Deactivated
2242 385 0 Bit4 Emergency start [0 ... 1] - r/w
3)
[1]
[0] Disable
[1] Manually enable/disable
194 389 0 USINT Input 1-Action [0 ... 45] - r/w
3)
[16]
[0] No action
[6] Manual operation local
[7] Emergency start
[10] Creep speed
[11] Quick-stop
[12] Reset
[16] Motor CW with PS1
[17] Motor CCW with PS1
[18] Motor CW with PS2
[19] Motor CCW with PS2
[20] Motor CW with PS3
[21] Motor CCW with PS3
[43] Motor standstill
[44] Use alternative stopping mode
[45] Pump cleaning mode
195 391 0 USINT Input 2-Action (see Input 1-Action) - r/w
3)
[0]
196 393 0 USINT Input 3-Action (see Input 1-Action) - r/w
3)
[0]
197 395 0 USINT Input 4-Action (see Input 1-Action) - r/w
3)
[12]

Table of Contents

Other manuals for Siemens SIRIUS 3RW5

Related product manuals