EasyManua.ls Logo

Siemens SIRIUS 3RW5 - Page 80

Siemens SIRIUS 3RW5
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.7 Assembly Object
SIRIUS 3RW5 EtherNet/IP communication module
80 Manual, 05/2019, A5E45131885002A/RS-AA/001
Instance 150 (0x96): Process image input (PII)
Only read access (get, r) to the process image input (PII) is possible.
Byte
Bit
Data format
Process image
3RW
52
1)
55
2)
0
0
BOOL
Ready (automatic)
r
r
1
BOOL
Motor On
r
r
2 BOOL Group error r r
3
BOOL
Group warning
r
r
4 BOOL Input 1 r r
5
BOOL
Input 2
-
r
6
BOOL
Input 3
-
r
7
BOOL
Input 4
-
r
1
0
BOOL
Motor current Iact-bit0
r
r
1
BOOL
Motor current Iact-bit1
r
r
2
BOOL
Motor current Iact-bit2
r
r
3
BOOL
Motor current Iact-bit3
r
r
4
BOOL
Motor current Iact-bit4
r
r
5
BOOL
Motor current Iact-bit5
r
r
6
BOOL
Manual operation local
r
r
7
BOOL
Ramp operation
r
r
2
0
BOOL
Motor CW
r
r
1
BOOL
Motor CCW
-
r
4
BOOL
Start mode active
r
r
5
BOOL
Operation / bypass active
r
r
6
BOOL
Stop mode active
r
r
7 BOOL Test operation active r
3)
r
3
0
BOOL
Thermal motor model overload
r
r
1
BOOL
Temperature sensor overload
r
r
2
BOOL
Switching element overload
r
r
3
BOOL
Cooling time active
r
r
4
BOOL
Device error
r
r
5 BOOL Automatic parameterization active - r
6
BOOL
New Ex parameter values detected
4)
-
r
4
0
REAL
Measured value 1
5)
(factory setting: Phase current I L1 (rms))
r
r
8
0
REAL
Measured value 2
5)
(factory setting: Phase current I L2 (rms))
r
r
12
0
REAL
Measured value 3
5)
(factory setting: Phase current I L3 (rms))
r
r
1)
Supported by SIRIUS 3RW52 soft starter
2)
Supported by SIRIUS 3RW55 soft starter
3)
From 3RW52 V2.0
4)
From 3RW55 V2.0
5)
You can parameterize the measured values for the 3RW55 soft starter. You will find more information in the
Equipment Manual of the 3RW5 soft starter and in the Dataset Object "Parameters".

Table of Contents

Other manuals for Siemens SIRIUS 3RW5

Related product manuals