Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
87
Bytes 16 ... 203 are filled with measured values (Page 90) and statistic data (Page 91).
Byte Bit Attribute ID
[byte]
Data format Soft starter diagnostics 3RW Type
3)
52
1)
55
2)
205 0 1401
[204 ... 205]
BOOL Device error r r ER
206 2 1405
[206 ... 210]
BOOL Motor heating active - r -
3 BOOL DC braking active - r -
4 BOOL Dynamic DC braking active - r -
5 BOOL Type of motor connection standard r r -
6 BOOL Inside-delta motor connection r r -
7 BOOL Motor connection type unknown r r -
207 0 BOOL Load missing r r ER
2 BOOL Phase failure L1 r r ER
3 BOOL Phase failure L2 r r ER
4 BOOL Phase failure L3 r r ER
5 BOOL Main power rotation right r r -
6 BOOL Main power rotation left r r -
209 0 BOOL Output 1 active r r -
1 BOOL Output 2 active r r -
2 BOOL Output 3 active r r -
3 BOOL Output 4 active - r -
4 BOOL Output 1 - Time active - r -
5 BOOL Output 2 - Time active - r -
7 BOOL Output 4 - Time active - r -
211 1 1407
[211]
BOOL Ready to start for motor ON r r -
3 BOOL Bypass defective r r ER
4 BOOL Bypass protective trip r r ER
5 BOOL Switching element L1 defective r r ER
6 BOOL Switching element L2 defective r r ER
7 BOOL Switching element L3 defective r r ER
212 2 1421
[212 ... 215]
BOOL Remaining time for tripping warning limit undershot - r MT
3 BOOL Motor heating warning limit exceeded r r MT
4 BOOL Current limit - maintenance demanded exceeded - r MT
5 BOOL Current limit - maintenance demanded undershot - r MT
6 BOOL Asymmetry limit warning exceeded - r MT
7 BOOL Ground fault limit warning exceeded - r MT
215 0 BOOL Pump cleaning active - r -
216 0 1422
[216 ... 217]
BOOL Thermal motor model deactivated r r -
3 BOOL Phase control failure r r ER
217 0 BOOL Switching element cooling time active r r -
1 BOOL Switching element too hot for Start r r MT
2 BOOL Current measuring range overshot r r ER