Parameter assignment
5.8 Setting parameterizing mode via key combination on the 3RW50 soft starter
SIRIUS 3RW50 soft starter
102 Manual, 09/2019, A5E35628455002A/RS-AA/001
5.8.2 Setting parameters in the parameterizing mode
Requirements
Activated parameterizing mode (Page 101)
Procedure
1. Select the desired parameter using the MODE key.
You can recognize your selection by the color of the STATE / OVERLOAD LED.
LED
STATE / OVERLOAD
Set parameter
Off
No selection
Lights up green
Control via digital input
Lights up red
Output ON / RUN
2. Change the setting of the selected parameter using the RESET / TEST key.
You can recognize your selection by the color combination of the three LEDs RN, ER and
MT.
Setting the parameter "Control via digital input" (selection in Step 1):
Control via digital input
"RN" LED
"ER" LED
"MT" LED
Set parameter value
Off
Off
Off
Manual activation
Off
Off
Lights up
yellow
Permanent activation
Off
Lights up red
Lights up
yellow
Activate on bus error
(factory setting)
Lights up
green
Lights up red
Lights up
yellow
No change on bus error