Messages and diagnosis
8.4 Faults and remedial actions of the 3RW50 soft starter
SIRIUS 3RW50 soft starter
168 Manual, 09/2019, A5E35628455002A/RS-AA/001
8.4 Faults and remedial actions of the 3RW50 soft starter
Display of the faults
The 3RW50 soft starter signals faults by means of the following displays:
● LED "ER" (red)
● 3RW5 HMI Standard (accessories)
● 3RW5 HMI High Feature (accessories)
Display of the faults on the 3RW5 HMI
● 3RW5 HMI Standard: The display shows fault numbers that you can assign to the
respective fault on the basis of the following table.
● 3RW5 HMI High Feature: Detailed information about faults and remedial actions appears
in plain text on the display.
Faults and remedial actions
303 Bus error -
• Acknowledgment via Auto
RESET
- - x
308 Switching element
defective
-
• Check switching elements
L1, L2, and L3.
• Replace the defective
devices.
- - -
309 Switching element
overload
Contact block
(switching contact, power
semiconductor) too hot
• Check the ambient
conditions associated
with cooling. You may
want to consider lowering
the operating
characteristics.
• Check the number of
switching operations.
• Acknowledgment after
cooling down
x x -
317 Electronics supply
voltage too low
The supply voltage is below
the permitted value.
• Check the power supply
(load dimensioning,
voltage range).
- - x
319 Supply voltage
missing
• The line side switch or
the power supply is not
plugged in correctly.
• No current
• Check the cables and the
cable connections and
replace any defective
components.
x x -