Example circuits
A.3 Special applications
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
219
A.3.3 EMERGENCY STOP shutdown to SIL 1 or PL c with a 3SK1 safety relay
The 3RW50 soft starter has no effect or influence on the safety function of the application.
For this reason, it is neither positively nor negatively considered in the safety application, and
also does not have to be included in the calculation for proof according to the standards.
If achievement of SILCL 1 according to IEC 62061:2005 or PL c according to
EN ISO 13849-1:2015 is required, the series connection of an additional contactor with the
3RW50 soft starter, in conjunction with a suitable safety relay (e.g.: 3SK1111), is required,
as well as monitoring of the contactor's auxiliary contacts.
Basic configuration
Emergency stop
3RT20 contactor
3RW50 soft starter
Motor
3SK1 safety relay