EasyManua.ls Logo

Siemens SIRIUS 3RW50 - 3.3 Mount the 3 RW50 soft starter on a level surface

Siemens SIRIUS 3RW50
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and dismantling
3.3 Mount the 3RW50 soft starter on a level surface
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
53
3.3 Mount the 3RW50 soft starter on a level surface
Requirements
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
Level surface, e.g. sufficiently strong mounting plate
4 properly executed drill holes with thread or plug on the level surface.
4 screws of suitable size and with regular thread for insertion into the selected mounting
plate or wall.
Use an additional four washers if the head of the screw is smaller than the specified
diameter.
Screwdriver (depending on the drive of the screws)
If necessary, use shims and snap rings.
Size
Article number
Screws
Tightening torque
Size S6
3RW505.-.....
M6
5 Nm
Size S12
3RW507.-.....
M8
8 Nm

Table of Contents

Related product manuals