Messages and diagnosis
8.5 Faults and remedial actions of the 3RW5 HMI High Feature
SIRIUS 3RW50 soft starter
172 Manual, 09/2019, A5E35628455002A/RS-AA/001
8.5 Faults and remedial actions of the 3RW5 HMI High Feature
Display of the faults on the 3RW5 HMI High Feature
Detailed information about faults and remedial actions appears in plain text on the display.
Faults and remedial actions
Error
Cause
Remedy
HMIFault Unrecoverable error detected after
internal diagnostics (self-test, etc.).
Replace the device.
FWUpdateUnsuccessful The firmware is incomplete and/or
the firmware expansions are
incomplete or incompatible.
Run a complete firmware update.
Check any occurring error messages.
Check to see whether or not the firmware
update was aborted.
FWUpdateInvalidSignature
Error during self-test Unrecoverable error detected after
internal diagnostics (self-test, etc.).
Replace the device.
No device answer The connection to the connected
soft starter has been interrupted.
Check the connection between the HMI and
the device.
Write Error File cannot be written to the
micro SD card.
Check whether the micro SD card is
inserted.
Check whether the micro SD card is
write-protected.
Loading language unsuccessful
The firmware is incomplete and/or
the firmware expansions are
incomplete or incompatible.
Run a complete firmware update.
Check any occurring error messages.
Check to see whether or not the firmware
update was aborted.
Invalid signature 'Load additional
language'