Messages and diagnosis
8.4 Faults and remedial actions of the 3RW50 soft starter
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
171
1479 Phase control failure
• Error appears without
motor start:
– Motor incorrectly
connected
– Inside-delta circuit
wrongly configured
– Ground fault
• Error appears while
motor is starting:
– Starting voltage too
high
• Check and correct the
wiring.
• Adapt parameters.
x x -
1482 Current measuring
range exceeded
• With sensors: The
measured value
exceeds the measuring
range
• With actuators: The
output value exceeds a
high limit value
• Check the interaction
between the module and
the sensor or actuator.
x x -
1523 Device error Unrecoverable error
detected after internal
diagnostics (self-test,
contactor contacts,
switching element, etc.).
• Replace the device.
• Please contact Technical
Support (Support
Request (Page 37)).
- - -
1605 Supply voltage
missing
• The line side switch or
the power supply is not
plugged in correctly.
• No current
• Check the cables and the
cable connections and
replace any defective
components.
x x -
1755 Overtemperature of
electronic
The temperature in the
components has exceeded
Check the ambient
temperature or the control
- - x
Visible on the display of the 3RW5 HMI Standard.
Acknowledgment via Manual RESET.
Acknowledgment via Remote RESET.
Acknowledgment via Auto RESET.
5)
Acknowledgment depends on parameter RESET MODE.