Messages and diagnosis
8.4 Faults and remedial actions of the 3RW50 soft starter
SIRIUS 3RW50 soft starter
170 Manual, 09/2019, A5E35628455002A/RS-AA/001
1408 Zero current after ON
command
No current flow is detected
after the motor feeder is
switched on. Possible
causes:
• Main circuit interrupted
(fuse, circuit breaker)
• Motor contactor or
contactor control is
defective
• No load
• Acknowledgment once
the cause has been
rectified.
x x -
The main power monitoring
detects a phase failure.
• Acknowledgment once
the cause has been
rectified.
x x -
1417 Bypass defective
• Bypass defective
• The error can also be
generated by
successive, brief
interruptions of the
control supply voltage.
• Check the bypasses for
L1, L2 and L3 and
replace any that are
defective.
• Please contact Technical
Support (Support
Request (Page 37)).
- - -
1418 Bypass protective
shutoff
An excessively high current
has occurred in bypass
mode.
• Check the motor.
• Check the dimensioning
of the soft starter.
• Acknowledgment after
cooling down
x x -
1454 Module slot wrong or
configuration faulty
There is a difference
between a real slot and a
slot configured in the
SIRIUS Soft Starter ES
(TIA Portal).
• Ensure consistency
between plugged and
configured module.
Possibly the referenced
module has a wiring error.
• After the cause is
eliminated, the error
self-acknowledges.
- - -
Switching element defective
• Check the contact blocks
for L1, L2, and L3 and
replace any that are
defective.
• Please contact Technical
Support (Support
Request (Page 37)).
- - -
1468 Contact 3 failed