Parameter assignment
5.2 Overview of parameters
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
93
5.2 Overview of parameters
Parameter
Symbol
Setting range
Factory setting
Tripping class for motor overload
protection
10A, 10E, 20E, OFF 10E
Rated operational current I
e
of the
motor
1)
1 ... 16
2)
1
Current limiting value as a multiple of
the set rated operational current I
e
of
the motor
1.3 ... 7 x I
e
max
The "max" setting corresponds to 7
times the maximum rated operating
current I
e
of the 3RW50 soft starter.
4 x I
e
Ramp up time
0 ... 20 s
If parameter value "0" is set, the
motor is switched on with a ramp up
time of approx. 100 ms.
10 s
Starting voltage
30 ... 100 % 30 %
Stopping time
0 ... 20 s 0 s
Soft torque
Off (LED off)
On (LED on)
Off
RESET MODE
Manual RESET (LED off)
Remote RESET (LED flashes green)
Auto RESET (LED lit green)
Manual RESET
1)
The rated operational current I
e
of the motor may, according to the standard, deviate by 20% from the rating plate
specification of the manufacturer.
2)
For meaning of scale, refer to laser-cut table on front panel of device.