Messages and diagnosis
8.4 Faults and remedial actions of the 3RW50 soft starter
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
169
Error
No.
1)
Error
Cause
Remedy
RESET MODE
Manual
2)
Remote
3)
Auto
4)
324 Temperature sensor
overload
The temperature of the
motor is too high.
Check the motor and the
application that is driven
by the motor.
After triggering, the motor
can only be switched on
again if the temperature
has reached the release
position of the
temperature sensor.
x
5)
x
5)
x
5)
325 Temperature sensor
wire break
A wire has broken in the
sensor cable of the
temperature sensor.
Check the sensor cable
and the temperature
sensor.
x
5)
x
5)
x
5)
326 Temperature sensor
short-circuit
A short-circuit has occurred
in the sensor line of the
temperature sensor.
Check the sensor cable
and the temperature
sensor.
x
5)
x
5)
x
5)
327 Therm. motor model
overload
The motor feeder is
overloaded.
The motor temperature
has exceeded a limit.
Check the motor and the
applications driven by the
motor.
You can switch on the
motor again after the
cooling-off period has
expired or after deleting
the thermal motor model.
x
5)
x
5)
x
5)
328 Motor overload
tripping
The motor feeder has
been overloaded
The temperature rise of
the motor has exceeded
a limit value
Check the motor and the
applications driven by the
motor.
You can switch on the
motor again after the
cooling-off period has
expired or after deleting
the thermal motor model.
x
5)
x
5)
x
5)
378 Invalid / inconsistent
firmware present
The firmware is incomplete
and / or the firmware
expansions are incomplete
or incompatible.
Execute a complete
firmware update.
Check any occurring error
messages.
Check to see whether the
firmware update has
been interrupted.
- - x
381 Device error Unrecoverable error
detected after internal
diagnostics (self-test,
contactor contacts,
switching element, etc.).
Replace the device.
Please contact Technical
Support (Support
Request (Page 37)).
- - -

Table of Contents