EasyManua.ls Logo

Siemens SIRIUS 3RW50 - Page 114

Siemens SIRIUS 3RW50
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter assignment
5.12 Parameterizing the High Feature 3RW5 HMI
SIRIUS 3RW50 soft starter
114 Manual, 09/2019, A5E35628455002A/RS-AA/001
Parameter
Description
Do Control After Logoff
This parameter describes the response after logging off while the motor is running.
Continue with motor control
The master control is retained by the 3RW5 HMI High Feature.
Stop motor and give back control (factory setting)
The motor stops and the master control is no longer with the
3RW5 HMI High Feature. Refer to Chapter
Operating modes and master control
function (Page 15).
Message display If errors and/or warnings are enabled, they will appear as pop-up windows in the
display of the 3RW5 HMI High Feature as soon as they occur.
Error
Enable (factory setting)
Disable
Warnings
Enable (factory setting)
Disable
Operation display Up to 5 different measured values can be selected from a list of measured values.
These measured values are then shown in the status display. You can find more
information on input actions in Chapter Monitoring the measured values of the
3RW50 soft starter with the 3RW5 HMI High Feature (Page 146).
Phase current average (%) (factory setting)
Phase current average (rms) (factory setting)
Phase current I L1 (rms) (factory setting)
Phase current I L2 (rms) (factory setting)
Phase current I L3 (rms) (factory setting)
Languages The required language is set in the "Languages" menu.
English (factory setting)
German
French
Spanish
Italian
Portuguese
Chinese
Additional language
1)
(Page 159)
1)
Only visible if an additional language has been added.

Table of Contents

Related product manuals