Functions   
7.1 Soft starting 
  SIRIUS 3RW50 soft starter 
122  Manual, 09/2019, A5E35628455002A/RS-AA/001 
Parameter 
 
Starting voltage  The starting voltage determines the starting torque of the motor. A lower 
starting voltage results in a lower switch-on torque and a lower starting 
current. Set the starting voltage to a value that ensures that the motor 
starts up immediately and smoothly once the start command reaches 
the 3RW50 soft starter. 
•  Factory setting: 30% 
•  Setting range: 30 ... 100 % 
Ramp up time  The ramp up time determines the time taken to increase the motor 
voltage from the parameterized starting voltage to the line voltage. This 
has an influence on the motor's acceleration torque which drives the 
load during the ramp-up operation. A longer ramp up time results in a 
shorter acceleration torque across the motor ramp up time. The motor 
therefore runs up more slowly and smoothly. 
Set the length of the ramp up time so that the motor can reach its rated 
speed by the time the end of the ramp up reached. The actual motor 
starting time is load-dependent and can differ from the parameterized 
ramp up time. 
If you choose a time that is too short, the ramp up time ends before the 
motor has accelerated to speed. A very high starting current that can 
reach the value of the direct starting current at this speed then occurs. 
In this case, the 3RW50 soft starter can switch itself off via the internal 
overload protection function and signal a fault. 
If parameter value "0" is set, the motor is switched on with a ramp up 
time of approx. 100 ms. 
•  Factory setting: 10 s 
•  Setting range: 0 ... 20 s