8.11 Emergency mode
8.11.1 Emergency start
Operating principle
The system can continue to be operated in the case of system faults with the "emergency start"
function. This is necessary for systems in which the product becomes unusable without
continued operation, e.g. glue and paint production. In crusher plants, in which a disconnection
makes any further startup impossible in certain situations, continued operation is also
necessary.
The emergency start is activated only if it has been enabled and a trip command exists due to a
system fault. The motor is switched on by means of a normal control command.
NOTICE
Damage to the system
If the Emergency start function is activated, both system defects and system protection
messages are ignored. This can cause further damage in the system.
In the case of some faults, the motor can be started via the "Emergency start" function despite
a pending group error:
Phase asymmetry limit exceeded
Electronic motor overload protection
Temperature sensor wire break
Temperature sensor short-circuit
Temperature sensor overload
Maximum starting time exceeded
I
e
limit value exceeded/undershot
Ground fault detected
Requirements
Ex operation not active
Functions
8.11 Emergency mode
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006 189