Parameter
Parameter Description
Local access protection Dene PIN
1)
PIN is set up and active (Page 238). In the factory setting, no
PIN is set up and the local access protection is not active.
Change PIN
2)
Existing PIN is changed (Page 239).
Delete PIN
2)
PIN is deactivated and deleted (Page 239).
Auto log o time
2)
If you do not regularly press a key on the 3RW5 HMI High
Feature, the current session will be terminated after the auto
logo time has elapsed.
• Factory setting: 0 min = deactivated
• Setting range: 0 ... 60 min
Log on
3)
Remove the local access protection by logging on with your 4-
digit PIN.
Log o
4)
Log out of your current session. The local access protection is
activated again. Alternatively, the session will be terminated
after the auto logo time.
1)
Menu item is displayed if no PIN has been dened.
2)
Menu item is displayed if a PIN has been dened.
3)
Menu item is displayed after logging o with an active PIN.
4)
Menu item is displayed after logging on with an active PIN.
8.23.2.1 Dene PIN
Requirements
• 3RW5 HMI High Feature
Menu: "Security > Local access protection"
• No PIN is dened (factory setting).
Procedure
1. Select the menu item "Dene PIN".
2. Using the navigation keys, set a 4-digit PIN and conrm your entry with the OK key.
3. The user information "HMI PIN dened" appears on the display of the 3RW5 HMI High Feature.
Conrm by pressing the OK key.
The 3RW5 HMI High Feature then returns to the "Local access protection" menu.
Result
You have dened the PIN and the set PIN is active.
Functions
8.23 Local access protection and user account administration
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
238 Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006