Parameter
Parameter Description
Local access protection De󹪝ne PIN
1)
PIN is set up and active (Page 238). In the factory setting, no
PIN is set up and the local access protection is not active.
Change PIN
2)
Existing PIN is changed (Page 239).
Delete PIN
2)
PIN is deactivated and deleted (Page 239).
Auto log o󹪜 time
2)
If you do not regularly press a key on the 3RW5 HMI High
Feature, the current session will be terminated after the auto
logo󹪜 time has elapsed.
Factory setting: 0 min = deactivated
Setting range: 0 ... 60 min
Log on
3)
Remove the local access protection by logging on with your 4-
digit PIN.
Log o󹪜
4)
Log out of your current session. The local access protection is
activated again. Alternatively, the session will be terminated
after the auto logo󹪜 time.
1)
Menu item is displayed if no PIN has been de󹪝ned.
2)
Menu item is displayed if a PIN has been de󹪝ned.
3)
Menu item is displayed after logging o󹪜 with an active PIN.
4)
Menu item is displayed after logging on with an active PIN.
8.23.2.1 De󹪝ne PIN
Requirements
3RW5 HMI High Feature
Menu: "Security > Local access protection"
No PIN is de󹪝ned (factory setting).
Procedure
1. Select the menu item "De󹪝ne PIN".
2. Using the navigation keys, set a 4-digit PIN and con󹪝rm your entry with the OK key.
3. The user information "HMI PIN de󹪝ned" appears on the display of the 3RW5 HMI High Feature.
Con󹪝rm by pressing the OK key.
The 3RW5 HMI High Feature then returns to the "Local access protection" menu.
Result
You have de󹪝ned the PIN and the set PIN is active.
Functions
8.23 Local access protection and user account administration
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
238 Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006