You have installed the 3RW5 HMI High Feature on a level surface and can commission
(Page 127) it.
4.4.4 Installing the 3RW5 HMI High Feature in the control cabinet door
Requirements
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
Removed 3RW5 HMI High Feature (Page 60)
HMI connecting cable (accessory) of suitable length connected to the 3RW55 or 3RW55
Failsafe soft starter
Cutout of suitable size in the control cabinet door
Depth of the 3RW5 HMI High Feature:
Total depth: 32 mm
Recessed depth: 26 mm
Permissible wall thickness of the control cabinet door:
Without IP65 door mounting kit: 1.5 to 3.0 mm
With IP65 door mounting kit: 1.0 to 7.0 mm
For using door mounting kit IP65:
IP65 door mounting kit (accessory)
The 󹪝xing brackets with marking "002" are intended for a 3RW5 HMI High Feature.
Screwdriver PZ2
Mounting and dismantling
4.4 Installing, mounting and removing the 3RW5 HMI High Feature
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
64 Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006