A.2.3 Actuation of a line contactor
Requirements
3RW55 soft starter
Parameterization required
WARNING
Automatic restart.
Can cause death or serious injury.
If a starting command is pending, a restart will be triggered automatically after the reset. This
particularly applies if the motor protection has tripped. Dangerous states of the system can
result.
Reset the start command (e.g. via the PLC or switch) before performing a reset.
To do this, for example, link the group error output (terminals 95 and 96) into the control.
Example circuits
A.2 Control circuit connection
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters