Requirements
• Valid rmware update
You will nd the latest rmware les on the 3RW5 topic page (
https://
support.industry.siemens.com/cs/ww/en/view/109747404).
• For operation of an application in Class I and Class II Hazardous Locations:
DANGER
Loss of the certied motor overload protection according to ATEX/IECEx.
Will cause death or serious injury.
A certied motor overload protection according to ATEX / IECEx is only provided for 3RW55
soft starters from rmware version V2.0 (does not apply to 3RW55 Failsafe soft starters).
Note that it is not permissible to downgrade to a previous rmware version because
otherwise certied motor overload protection according to ATEX / IECEx cannot be
guaranteed.
Procedure
1. Make sure that the motor is switched o and you do not start the motor during the rmware
update.
A control command for starting the motor is not supported during the rmware update.
To ensure the quickest and most fault-free rmware update, it is recommended that you
disconnect the main supply voltage (operational voltage) of the 3RW55 and 3RW55 Failsafe
soft starters and put the CPU / PLC into the STOP state.
2. Perform the update of the device rmware.
The following procedures are possible:
– With a micro SD card via the 3RW5 HMI High Feature (Page 277)
– Via the local interface of the 3RW5 HMI High Feature with SIRIUS Soft Starter ES
(TIA Portal)
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Online & Diagnostics" > Window "Work area" > "Soft Starter /
3RW5 communication module used / HMI > Functions > Firmware Update"
– With a eldbus via a 3RW5 communication module with SIRIUS Soft Starter ES (TIA Portal)
Premium / Professional or the conguration software of the controller (e.g. STEP 7 with
corresponding HSP) (via a 3RW5 PROFINET or PROFIBUS communication module only)
Note
Firmware update of the 3RW5 PROFINET High Feature communication module
The rmware update of the 3RW5 PROFINET High Feature communication module via SIRIUS
Soft Starter ES (TIA Portal) at the local interface or using a micro SD card via the 3RW5 HMI
High Feature can take a very long time in comparison with other options (up to about
60 minutes).
Maintenance and service
10.3 Firmware update
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
276 Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006