Integrating the library contents
6.2 Working with the library in WinCC flexible
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
76 Function Manual, 11.2017, A5E37764016-06-76
Inserting faceplates
Procedure
Table 6- 7
In the "Project" view, open the project into which you want to insert the faceplate.
2 Open the library “PSU8600 V2-3 library WinCC flexible 2008” in your project.
3 In your project, open the screen into which you want to insert the faceplates.
Select the “Faceplates_PSU8600” folder of the library.
Drag and drop the “Faceplates_PSU8600” faceplate onto the screen area.
6 Select the “PSU8600” folder in the library. Drag and drop the “PSU8600” folder to the "Tags" folder under
“Communication” folder in your project.
In the "Project" window, navigate to “Screens > Template”.
Select the “HMI Alarm views” folder in the library. Drag and drop two message windows into the template.
9 Select "Alarm_window_PSU_Pending" alarm window, right-click on the "Properties" and select "Properties >
Display > Enable "ACK" button. Repeat the same procedure for enabling "ACK" button in
"Alarm_window_PSU_History" alarm window.
In the "Project' window, navigate through the folders “Communication > Tags" and open "PSU8600”.
11 Check the connection name entered for the control tags.
The connection name must be identical with the name of the connection you created for the configured con-
nection to your controller.