EasyManua.ls Logo

Siemens SITRANS MAG 6000 I - Page 16

Siemens SITRANS MAG 6000 I
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Special conditions for ATEX 2 GD
It is required that:
The equipment is supplied with its current output (terminals 31 and 32) in "Passive mode
only".
The external connections to terminals 85 and 86 shall comply with the following:
The wire conductors shall have a cross-sectional area between 0.5 mm
2
and 2.5 mm
2
.
No more than one single or multiple strand wire conductor shall normally be connected
to each of the terminals. If multiple conductors are required, these shall be joined in a
suitable manner, e.g. two conductors into a single insulated crimped boot lace ferrule.
The insulation on the wire conductors shall extend to within 1 mm of the metal of the
terminal throat.
The terminal screws shall be tightened down with a torque between 0.4 Nm and 0.45
Nm.
The equipment shall not be opened when an explosive gas or dust atmosphere may be
present.
The equipment internal circuits at the following terminals are not capable of withstanding
a 500 V r.m.s. a.c. test to earth as required by clause 6.3.12 of EN 60079-11-2007. This
must be taken into account in any equipment installation:
Terminals 77 and 78 – Digital input.
Terminals 95 and 96 – Foundation Fieldbus/Profibus (FISCO). (Not applicable to Model
7ME693-2BA6)
Terminals 0, 81, 82, 83 and 84 – Sensor electrode input (Remote Version only).
electrical connections are in accordance with national requirements for installation of
electrical systems in hazardous areas, e.g. EN60079-14 in Europe.
the protective cover for the power terminals is properly installed.
When the device is de-energized, the power supply terminal room may be opened because
the non-intrinsically safe power terminals are separately covered. Only remove protective
cover when device is de-energized.
sensor and transmitter are connected to the potential equalizing conductor.
when protective earth (PE) is connected, no potential difference between the protective
earth (PE) and the potential equalization (PA) can exist, even during a fault condition.
Safety notes
2.3 Installation in hazardous area
16
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018, A5E02083319-AH

Table of Contents

Related product manuals