A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 97
G: Hazardous Installation
Wiring setups for hazardous area installations
Always check the device nameplate and process device tag to verify the approval rating.
1. Intrinsically Safe wiring
For power demands see “Loop Voltage versus Loop Resistance” on page 95.
For wiring requirements: follow local regulations.
Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67
, IP68 locations.
Refer to “Instructions specific to hazardous area installations (Reference European
ATEX Directive 2014/34/EU, Annex II, 1/0/6)” on page 98.
2. Non-incendive wiring (FM US only)
For power demands, see “Loop Voltage versus Loop Resistance” on page 95 of
Appendix A.
Serial No: GYZ / B1034567
Power Rating: 24V
Max., 4-20 mA
Nom., 30V
U
i
=30V
I
i
=120mA
P
i
=0.8W
C
i
= 3.6 nF
L
i
=0 mH
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7MLxxxx-xxxxx-xxxx
Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: 40°C to 80°C
HART
Ex ia IIC T4 Ga
DNV 12.0070 X
0518
1G
ExiaIICT4Ga
II
SIRA 06ATEX2355X
IECEx SIR 13.0008X
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA - VEJA INSTRUÇÕES
KCC-REM-S49
PROBELU
The ATEX certificate can be downloaded from the product
page of our website at: www.siemens.com/probelu
. Go to Support > Approvals /
Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch
and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 13.0008X.
Device nameplate (ATEX/IECEX/INMETRO/RCM)
Serial No: GYZ / S1034567
Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: 40°C to 80°C
Power Rating: 24V
Max., 4-20 mA
Nom., 30V
WARNING: Possible static hazard, do not rub or clean on site.
Class I, Div 1, Group A, B, C, D
Class II, Div 1, Group E, F, G
Class III
Temp. Code: T4
CSA per drawing: 23650517
FM per drawing: 23650516
HART
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7ML1234-78910-ABC-D
159134
Vmax=30V
Imax=120mA
Pmax = 0.8 W
Ci=3.6nF
Li=0.5mH
FM Intrinsically Safe connection drawing number 23650516, and CSA Intrinsically Safe
connection drawing number 23650517 can be downloaded from the product page of our
website at: www.siemens.com/probelu
. Go to Support > Installation Drawings > Level
Measurement > Continuous - Ultrasonic.
Device nameplate (FM/CSA)
Class I,Div.2,
Group A, B, C,D
Temp.Code:T5
HART
Serial No: GYZ / S1034567
Encl.:
NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: 40°C to 80°C
Power Rating: 24V
Max., 4-20 mA
Nom., 30V
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7ML1234-78910-ABC-D
FM Class 1, Div 2 connection drawing
number 23650583 can be downloaded from the product page of our website at:
www.siemens.com/probelu
. Go to Support > Installation Drawings > Level Measurement >
Continuous - Ultrasonic.