EasyManua.ls Logo

Siemens sitrans PROBE LU - Mechanical and Interface Specifications

Siemens sitrans PROBE LU
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 8 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS A5E32337695
Specifications
Blanking distance
3
0.25 m (0.82 ft)
Update time at 4mA 5 s
Beam angle 10
o
at –3 dB boundary
Temperature compensation built in to compensate over temperature range
Memory non-volatile EEPROM,
no battery required
Interface
HART standard, integral to analog output
configuration Siemens SIMATIC PDM (PC), or HART handheld
communicator, or Siemens infrared handheld
programmer
analog output 4–20 mA
± 0.02 mA accuracy
display (local) multi-segment alphanumeric liquid crystal with Bar
graph (representing level)
Programmer (infrared keypad)
Siemens Infrared IS (Intrinsically Safe) Handheld Programmer: for all locations, including
hazardous.
approval ATEX II 1GD, Ex ia IIC T4 Ga, Ex iaD 20 T135 °C,
SIRA 01ATEX2147
IECEx SIR 09.0073 Ex ia IIC T4 Ga, Ex iaD 20 T135 °C
FM/CSA Class I, Div. 1, Groups A, B, C, D
INMETRO DNV 12.0075
Ex ia IIC T4 Ga
Ex ia IIIC T135 °C Da
DNV #OCP 0017
ABNT NBR IEC 60079-0:2008
ABNT NBR IEC 60079-11:2009
ABNT NBR IEC 60079-26:2008 e IEC 61241-11:2005
ambient temperature 20 to +50 °C (5 to +122 °F)
interface proprietary infrared pulse signal
power 3V lithium battery (non-replaceable)
weight 150 g (0.3 lb)
color black
Mechanical
Process Connections
threaded connection 2” NPT, BSP, or G (EN ISO 228-1) / PF2 (JIS B 0202)
flange connections 3" (80 mm) universal flange
other connections FMS 200 mounting bracket, or customer-supplied
mount
Transducer (2 options)
ETFE (ethylene-tetrafluoroethylene), or
PVDF (polyvinylidene fluoride)

Table of Contents

Other manuals for Siemens sitrans PROBE LU

Related product manuals