EasyManua.ls Logo

Siemens sitrans PROBE LU - Diagnostic Tests (P900 to P924)

Siemens sitrans PROBE LU
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 63
Parameters
P839 TVT Hover Level
Defines (in percent) how high the TVT curve is placed above the profile, relative to the
largest echo. When SITRANS Probe LU is located in the center of the vessel, lower this
parameter to prevent multiple echo detections.
Diagnostic Tests (P900 to P924)
P900 Software Revision Number
Displays the software revision level.
1. Select P90 0.
2. The secondary index number is visible in the auxiliary reading field.
3. Press DISPLAY twice to focus control on the secondary index (the auxiliary
reading field goes blank).
4. Key in the index number required, and press ENTER .
5. The software revision level associated with the new secondary index appears.
6. Press DISPLAY twice and use the ARROW keys or enter the value for the next
desired parameter.
Values
Range 0 to 100%
Default 33 (%)
Values (view only)
Range 0.00 to 99.99
Secondary index
1 Main code revision
2 Primary boot revision
3 Alternative boot revision
4 Hardware stack revision
Default Determined by the software revisions installed

Table of Contents

Other manuals for Siemens sitrans PROBE LU

Related product manuals