Page 64 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS A5E32337695
Parameters
P901 Memory Test
Press ENTER to activate the test.
Measurement
P911 mA Output Value
Access this parameter to display the current value of the mA output.
1. Set P201 to 0 (manual).
2. Enter a test value.
P912 Temperature
Displays the temperature in
o
C (as monitored by the connected transducer). This value is
not affected by Temperature Source (P660).
Values (view only)
IdLE Normal operation
PAS S Memory test successful
F1 Fail RAM
F2 Fail EEPROM
F3 Fail FLASH
Values (HART)
Range 3.6 to 22.6 (mA)
Default 4 mA in HART fixed current mode
Note: P201 must be set to 0 to enable the test value to be entered at P911: be sure to
restore P201 to the previous setting after the test!
Values (view only)
Range
–40 to 85 (
o
C)