Page 22 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS A5E32337695
Operation
Master Reset (P999)
Resets all parameters to their factory settings, with the following exceptions:
• P000 and P069 are not reset.
• The learned TVT curve is not lost.
1. Press PROGRAM then DISPLAY to activate PROGRAM mode.
2. Press DISPLAY to open parameter fields.
3. Key in 999.
Press CLEAR then ENTER , to Clear All
and initiate reset. The LCD displays C.ALL.
4. Reset complete. (Reset takes several seconds
to complete.)
Using Units or Percent (%)
Many parameters can be viewed either as a percentage, or in measurement units (P005).
View the parameter, then press MODE to toggle between units and percentage.
Setup Steps (outline)
Set the Quick Start parameters between P001 and P010 (the main settings that apply to all
applications and make the system operational). Then set P837 and 838 to ignore false
echoes, and return to RUN mode.
1. Select a language option
1
, or numeric, for the auxiliary reading (P010).
2. Select the measurement mode: level, space, or distance (P001).
3. Set the response time to level changes (P003).
4. Select units of measurement: m, cm, mm, ft, or in. (P005).
5. Set process empty level (Empty: P006).
6. Set the range to be measured (Span: P007).
7. To ignore false echoes before the material echo, set Auto False-Echo Suppression
Distance P838.
8. Enable Auto False-Echo Suppression P837.
9. Return to RUN mode.
Note: Following a Master Reset, complete programming is required.
1.
The language options are English, German, French, or Spanish. The parameter title appears in
the language selected, for the first 10 parameters.