A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 37
Parameters
P052 Vessel Dimension A
Dimension A as used for P050 Vessel Shapes 2, 3, 4, 5, or 7, in the chart on page 36.
Enter one of the following, using the units selected in P005:
• height of the vessel bottom if P050 = 2, 3, 4, or 5
• length of one end-section of the vessel if P050 = 7
P053 Vessel Dimension L
Dimension L as used in P050 Vessel Shape 7
,
in the chart on page 36.
Enter the vessel length L (excluding both end sections) if P050 = 7. Use the units selected
in P005.
P054 Level or Head Breakpoints
P054 and 055 can be used to calculate either level and volume in a vessel, or head level
and flow rate in an open channel device. (For more information on Open Channel
Monitoring, please see Open Channel Monitoring (OCM) on page 91).
Level Breakpoints
When the vessel shape is too complex for any of the preconfigured shapes, you can
define the shape as a series of segments. In P054 you assign a level value to each
breakpoint. In P055 you assign a corresponding volume value to each breakpoint.
Values
Range 0.0000 to 99999 in units (P005)
Default 0.0
- - - -
Display when P050 = 0
Related Parameters
P050 Vessel Shape
Values
Range 0.0000 to 99999 in units (P005)
Default 0.0
- - - -
Display when P050 = 0
Related Parameters
P050 Vessel Shape
Primary Index
P054
Secondary Index
Breakpoint number
Values
Range 0.0000 to 99999 in units (P005)
Default 0.000
Related Parameters
P055 Volume or Flow Breakpoints