Scale parameters and functions
8.26 DR 29 Configuration of technology messages
SIWAREX WP251
134 Manual, 12/2015, A5E37203357A
- - B16_7 1 rw 1 0 1 1816
2101 Risk of overfilling Current configuration would
lead to overfilling during dosing
(is checked at multiple points
during dosing (e.g. after taring))
B16_8 0 rw 1 0 1 1816
2102 Coarse shut-off
point already exceed-
The coarse shut-off point is
already exceeded before
switching on the coarse signal
B16_9 0 rw 1 0 1 1816
2103 No standstill A required standstill did not
occur somewhere during dosing
B16_10 0 rw 1 0 1 1816
2104 CPU in "STOP" No stand-alone operation and
no CPU or CPU is not running
B16_11 0 rw 1 0 1 1816
2105 Set point too
small
The set point for the dosing is
too small in the current configu-
B16_12 0 rw 1 0 1 1816
2106 Error fine weight Trailing weight, shut-off correc-
tion value and set point are not
B16_13 0 rw 1 0 1 1816
2107 Stop after toler-
ance error
Weighing cycle stopped after
tolerance error based on pa-
B16_14 0 rw 1 0 1 1816
2109 Blocking time
"coarse" error
Blocking time coarse signal
After expiration of the blocking
time coarse signal, the coarse
shut-off point was already ex-
B17_0 0 rw 1 0 1 1817
2110 Blocking time
"fine" error
Blocking time fine signal viola-
tion After expiration of the
blocking time fine signal, the
fine shut-off point was already
B17_1 0 rw 1 0 1 1817
2111 Maximum weigh-
Maximum dosing time was
B17_2 0 rw 1 0 1 1817
2112 Logging not
possible - no standstill
Logging conditions (standstill 2
and/or SecureDisplay not
shown) are not met, automatic
logging cannot be performed
B17_3 0 rw 1 0 1 1817
2113 Maximum empty-
ing time exceeded
Emptying monitoring time ex-
pired without achieving empty
B17_4 0 rw 1 0 1 1817
2114 Maximum correc-
tive action exceeded
Maximum corrective action
(defined in DR 24) was ex-
ceeded
B17_5 0 rw 1 0 1 1817
2115 Log error Error while reading a log entry
(refresh DS 46 with Request ID
B17_6 0 rw 1 0 1 1817