Scale parameters and functions
8.6 DR 5 Tare / zero memory
SIWAREX WP251
Manual, 12/2015, A5E37203357A
81
Variable
Note
Type
Length
(bytes)
Read/
write
protec-
tion
Default
Min.
Max.
Modbus
Register
Version identi-
fier
Current data record
version information
USHORT
2
r
1
1
65635
1217
Effective tare
weight - from
specification 1,
2 or 3
(Page 81)
Current tare weight
(tare setting)
FLOAT 4 rwP 0 0 Depends
on speci-
fication in
DR 3
1218
Effective tare
weight (semi-
automatic)
(Page 81)
Current tare weight
(semi-automatic)
FLOAT 4 rwP 0 0 Depends
on speci-
fication in
DR 3
1220
Zero by power-
on (value when
switching on)
(Page 82)
Current zeroing
weight (affected by
switch-on)
FLOAT 4 rwP 0 Depends
on speci-
fication in
DR 3
Depends
on speci-
fication in
DR 3
1222
Zero weight
(semi-
automatic)
(Page 82)
Current zero setting
weight (semi-
automatic)
FLOAT 4 rwP 0 Depends
on speci-
fication in
DR 3
Depends
on speci-
fication in
DR 3
1224
Current zero
tracking weight
(Page 82)
Current zero setting
weight
(zero tracking)
FLOAT 4 rwP 0
Depends
on speci-
fication in
DR 3
Depends
on speci-
fication in
DR 3
1226
Dead load
(Page 82)
Dead load calculat-
ed during automatic
calibration
FLOAT 4 r 0
Depends
on speci-
fication in
DR 3
Depends
on speci-
fication in
DR 3
1228
Reserve 1
Reserve
SHORT
2
rw
0
-
-
1230
Reserve 2
Reserve
USHORT
2
rw
0
-
-
1231
Reserve 3
Reserve
FLOAT
4
rw
0
-
-
1232
8.6.2
Effective tare weight - from specification 1, 2 or 3
A preset tare weight can be specified in data record DR 15. It is activated with command
(1013). The "Delete Tare" command deactivates the preset tare weight. This does not delete
the specification in data record DR 15.
8.6.3
Effective tare weight (semi-automatic)
The corresponding command (see command 1011) applies the current gross weight as the
active tare weight. From this point on, the activated tare weight is factored into the weight
calculations. The "Delete tare" command deactivates the active tare weight.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WP251 and is the answer not in the manual?

Siemens SIWAREX WP251 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WP251
CategoryAccessories
LanguageEnglish

Related product manuals