Scale parameters and functions
8.7 DR 6 Limits
SIWAREX WP251
Manual, 12/2015, A5E37203357A
83
Variable
Note
Type
Length
(bytes)
Rw
Default
Min.
Max.
Modbus
Register
Application
Information about
which application
the DR belongs to
USHORT
2
r
105
-
-
1236
Version identifier
Current data rec-
ord version infor-
mation
USHORT
2
r
1
1
65635
1237
Limit reference (limits
1 and 2)
Gross / net refer-
ence of limit 1 and
2
0: Limit 1 and
Limit 2 reference
the gross weight
(specification in %
of max. weight
from DR 3)
1: Limit 1 and Limit
2 reference the net
weight (specifica-
tion in % of max.
weight from DR 3)
2: Limit 1 and Limit
2 reference the
gross weight
(specification as
absolute weight
value)
3: Limit 1 and Limit
2 reference the net
weight (specifica-
tion as absolute
weight value)
USHORT 2 rw 0 0 1 1238
Reserve 1
Reserve
USHORT
2
rw
0
0
-
1239
Limit value 1 ON, limit
value 2 ON, limit
value 1 OFF, limit
value 2 OFF
(Page 84)
Switch-on point for
Limit 1
FLOAT 4 rw 0 maxi-
mum
num-
ber
range
maxi-
mum
num-
ber
range
1240
Reserve Reserve DINT 4 rw 0 0 maxi-
mum
num-
ber
range+
1242
Limit value 1 ON, limit
value 2 ON, limit
value 1 OFF, limit
value 2 OFF
(Page 84)
Switch-off point for
Limit 1
FLOAT 4 rw 0 maxi-
mum
num-
ber
range
maxi-
mum
num-
ber
range
1244

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WP251 and is the answer not in the manual?

Siemens SIWAREX WP251 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WP251
CategoryAccessories
LanguageEnglish

Related product manuals