Note the following points with regard to the deviation message:
Notes on use and
configuration
• Set the message delay time long enough so that the plant does not trigger a
fault status message on startup
• The deviation message always refers to the sequence controller. Therefore, in
the case of room-supply air temperature cascade control, it monitors the supply
air. Set the values accordingly
• The deviation message only works when the control process is active
• If a sequence is limited by a general or sequence limiter, it will not generate a
deviation message
• The assignment is made in the configuration diagram, always at sequence
controller 1
• If you set both the deviation message and the timeout period for the sequence
controller, ensure that the message delay time for the deviation message is
longer than the timeout period
If you fail to do so, there will be a deviation message every time the timeout acts
on the sequence controller
9.11.3 Settings
Path: … > COMMIS > CONF > CTLOOP 1
Configuration
Display Name Range / comments
DV ALM Deviation message Activation of “Deviation message” function,
adjustable values:
---, Q1, Q2, … (relays only)
Path: … > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display Name Range Factory setting
DV ALM Deviation message Main controlled variable
input signal range
100 K, 100 %,
900.0, 9000
DV DLYH Deviation message
delay high
00.00…6.00 h.m 00.30 h.m
DV DLYL Deviation message
delay low
00.00…6.00 h.m 00.30 h.m
Path: INFO
Display values
Display Name Comments
DV ALM Deviation message Indication of current state:
Off, On
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
DV ALM Deviation message Off, On