18
Once a minute, the 4100 software performs a self-alarm test of each TrueAlarm
sensor. The self-alarm test raises
the value of each sensor to a value that simulates an alarm condition. If the sensor reports back a value that is not
within the alarm range, a self-test abnormal trouble will be displayed for that specific sensor.
The following paragraphs discuss the responsibilities of 4100 system operators when these trouble indications
occur.
ALMOST DIRTY INDICATION
Using the front panel keypads, it is possible for a SIMPLEX Field Service representative to turn on a system point
that allows an almost dirty sensor to report a trouble. Although the almost dirty sensor is holding its sensitivity level,
the 4100 operator can schedule maintenance for the sensor before the dirty sensor trouble occurs.
DIRTY INDICATION
A Dirty indication means that the sensor is holding its sensitivity level, but that the 4100 operator should schedule
maintenance for the sensor. Clean the sensor as required and, if necessary, call Simplex for service.
EXCESSIVELY DIRTY INDICATION
The Excessively Dirty indication means that the sensor is no longer compensating for dirt and dust. Because false
alarms are possible with this condition, sensors must be cleaned as soon as possible. If necessary, call Simplex for
service.
SELF-TEST ABNORMAL INDICATION
All 4100 system sensors are automatically tested once every minute. If a sensor fails to report properly to the 4100
master controller, a self-test abnormal condition occurs. Since the sensor is not working properly, it must be
replaced. Replace it, or call Simplex for service.
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000

Related product manuals