13
SECTION 3
TROUBLE CONDITIONS
INTRODUCTION
NOTE: Refer to Figure 3 for locations of interface panel LEDs and keys.
When a System Trouble Condition is detected by the 4100, the condition is indicated by the following:
Yellow SYSTEM TROUBLE LED on the interface panel is flashing
Tone-alert sounds steady
Annunciator LEDs may be illuminated
Alphanumeric display on the interface panel shows the following message.
The interface panel has a yellow SYSTEM TROUBLE LED which lights whenever a trouble is present in the system.
When a trouble occurs, the LED flashes, the tone-alert sounds steady, and a trouble message appears on the
alphanumeric display. The trouble LED glows steady and the tone-alert silences when the <TBL ACK> key is
pressed.
When Global Acknowledge is used, and the trouble clears, the system automatically clears without user intervention.
After approximately 30 seconds, the system alphanumeric display should indicate a normal system, as shown below.
When Individual Acknowledge is used, the tone-alert re-sounds when the condition clears. The <TBL ACK> key
must be pressed twice (once to change from Alarm Summary to actual point, and once to acknowledge the
condition). After a delay, the system alphanumeric display should indicate a normal system.
GLOBAL ACKNOWLEDGE PANEL OPERATION DURING TROUBLE CONDITIONS
Figure 3
Interface Panel Showing Trouble Condition
**TROUBLE**
FIRE = 0 PRI2 = 0 SUPV = 0 TRBL = 1
Press <ACK> to review.
SYSTEM IS NORMAL
8:32:45 MON 04-APR-94
ALPHANUMERIC DISPLAY
ACKNOWLEDGE KEY
YELLOW SYSTEM TROUBLE LED
ACKNOWLEDGE
FIRE
ALARM
ALARM
ACK
PRIORITY 2
ALARM
SYSTEM
SUPV
SUPERVISORY
ACK
SYSTEM
TBL
TROUBLE
ACK
ALARM
ALARM
SILENCED
SILENCE
POWER
SYSTEM
ON
RESET
ALARM
ACK
**TROUBLE** Press <ACK> to review points.
FIRE = 0PRI2 = 0SUPV = 0TRBL = 1
(FLASHING)
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000

Related product manuals