The system is default-programmed to allow the Walk Test
to be performed without sounding audible signals. (See
Silent Walk Test
and Sig/No Sig.) The Walk Test
will not activate any point which is disabled. Therefore, you
have the ability to manually exclude any point from the test. (See How to Disable a Point.)
You may enable the logging of Walk Test
events, which allows each zone with an abnormal condition to be time
tagged and added to the trouble log. This is beneficial when a 100% silent Walk Test
, without visuals, is required.
When testing the devices, use the alarm LED on the smoke detector, or a simple delay, to know when to continue
to the next device. After test completion, check the log to verify that all zones activated the correct number of times
and in the correct order.
ZONE CODING OPTION
The system supports two types of audible signalling to indicate an alarm condition on a zone. By default, zone
coding is used. This code matches the ZONE number associated with that point. The zone code is only used the
first time a zone is reported. For subsequent alarms on the same zone, a single 0 CODE (two short pulses) is used.
Examples of Zone Coding are shown below.
NOTE: Zero Code = 2 short pulses
Zone coding may be disabled for each of the eight Walk Test
groups, Group 0 through Group 7, using the interface
panels display. When zone coding is disabled (<F3> key to ZERO), a 0 code is always used, even for the first
alarm. This method of testing is more appropriate for maintenance testing, once all wiring is verified.
When a control point is pulsed by Walk Test
, it is done without affecting the priority of that point regardless of its
present value. This guarantees that Walk Test
does not interfere with any required SMPL (software) operations
during a real alarm.
MAPNET II
monitor devices sound the zone code, with the first digit being the channel number, followed by the
devices address number. Example: M1-1 sounds a 1,1 code. M4-123 sounds a 4, 1, 2, 3 code. MAPNET II
signal
devices cannot annunciate codes.
SILENT Walk Test
The control points to be activated (pulsed) during Walk Test
are determined by the contents of the control lists
which are configured when programmed. Several options are available when configuring a silent Walk Test
control
list. The first option is to NOT put any audible signals into the control list. The second option is to disable the audible
control points from the front panel, one at a time. The last option is to use the NO<sig option (controlled by the
<F4> key) when in the Walk Test
menu. If this last option is selected, none of the points in the control list will code
(see Sig/No Sig).
ENTERING Walk Test
MODE
Walk Test
is enabled through the interface panels alphanumeric LCD (Liquid Crystal Display). Walk Test
is
passcode protected. The Walk Test
menu will not appear unless the operator is at the proper access level. To enter
one of these levels, press the menu key, select the Change Access Level option, press the <F1> key to log in, and
then type in the correct passcode for the level you desire.
Select the Enable Walk Test
option on the Main Menu, and press the ENTER key. Then use the following
FUNCTION KEYS (<F1> through <F4>) to select the various Walk Test
options.
<F1> Key Enables/disables the Walk Test
group. Press this key to enter Walk Test
for the specified
group. Press the key again to exit Walk Test
.
= Zone 3 (three long pulses)
= Zone 12 (one long, pause, two long pulses)
= Zone 20 (two long and two short pulses)
= Zone 102 (one long, two short, and two long pulses)
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000