78
2. Press the <ON> key. A typical display is shown below.
3. Press the <ENTER> key. A typical display is shown below.
4. Press the <CLR> key. The display shows the following message.
HOW TO RETURN A POINT TO AUTO
The <AUTO> key press leaves a point in its current state (ON or OFF), but allows the system program to control it.
AUTO is the normal state for all control points. A trouble exists if any control point is taken out of the AUTO state.
The point to be turned to AUTO must first be identified to the system. This is accomplished by selecting/entering the
required point on the alphanumeric display, and then pressing the <AUTO> key. If the <AUTO> key is passcode
protected, perform the Log In Procedures.
To return a point to AUTO, perform the following procedures.
1. Ensure the point to be turned to AUTO is shown on the alphanumeric display. A typical point (SIG2) is
shown below.
2. Press the <AUTO> key. A typical display is shown below.
3. Press the <ENTER> key. A typical display is shown below.
Press <ENTER> to force ON
SIGNAL CIRCUIT: SIG2
MASTER SIGNAL POINT 2, SIG2
SIGNAL CIRCUIT
ON
**TROUBLE**
FIRE = 0 PRI2 = 0 SUPV = 0 TRBL = 1
Press <ACK> to review.
MASTER SIGNAL POINT 2, SIG2
SIGNAL CIRCUIT
OFF
Press <ENTER> for AUTOmatic control
SIGNAL CIRCUIT: SIG2
MASTER SIGNAL POINT 2, SIG2
SIGNAL CIRCUIT OFF
OFF
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000