During automatic alarm conditions, operate the microphone in the following manner.
Figure 13
LED/Switch Locations for Microphone Operation
During Alarm Conditions (Single Channel)
ALL
SPEAKERS
EVAC
SELECTIVE
EVAC
ALL
SPEAKERS
TALK
LOCAL
SPEAKER
FLR 1
FLR 2
FLR 3
FLR 8
FLR 4
FLR 5
FLR 6
FLR 7
A
PHONE
PHONE 1
PHONE 2
PHONE 7
PHONE 8
PHONE 9
PHONE 10
PHONE 15
SILENCE
PHONE 3
PHONE 4
PHONE 5
PHONE 6
PHONE 11
PHONE 12
PHONE 13
PHONE 14
C
D
ALARM
SILENCE
B
HOW TO MANUALLY INITIATE AN EVACUATION SIGNAL (SEE FIGURE 14)
1. Press the <ALARM SILENCE> key, if desired.
This will turn OFF the alarm signals/messages.
NOTE: To talk to all areas in alarm, go to Step
3.
2. To talk to ALL areas:
Turn ON (UP) ALL SPEAKERS TALK Switch
(Item A) and go to Step 3.
To talk to SPECIFIC areas:
Turn ON/OFF desired Speaker Select Switches
(Item B).
3. Remove the microphone from the cradle; press
the Talk switch (Item C). Wait for the green
TALK LED to turn ON (Item D).
4. Make the appropriate announcement.
5. When finished, unkey the microphone and
place it in the cradle. In an Alarm condition,
unkeying the mike may play a pre-selected
tone over the speaker circuits which are still
active (unless <ALARM SILENCE> is
selected).
6. Turn OFF (DOWN) ALL SPEAKERS TALK
Switch and/or activated Speaker Select
Switches (Items A and B).
To manually initiate an evacuation signal, do the
following.
1. To evacuate ALL areas:
Turn ON (UP) ALL SPEAKERS EVAC Switch
(Item A).
To evacuate specific areas:
a. Turn ON (UP) desired Speaker Select
Switches (Item B).
b. Turn ON (UP) SELECTIVE EVAC Switch
(Item C).
2. To turn OFF all EVAC operations, turn OFF
(DOWN) the ALL SPEAKERS EVAC Switch
(Item A).
Figure 14
LED/Switch Locations for Evacuation Signal
Initiation (Single Channel)
ALL
SPEAKERS
EVAC
SELECTIVE
EVAC
ALL
SPEAKERS
TALK
LOCAL
SPEAKER
FLR 1
FLR 2
FLR 3
FLR 8
FLR 4
FLR 5
FLR 6
FLR 7
B
A
C
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000