DUAL CHANNEL AUDIO OPERATIONS
The following paragraphs discuss 4100 Dual Channel Audio Operations.
AUDIO CONTROL LED/SWITCH MODULE FOR DUAL CHANNEL AUDIO
The Audio Control Module contains eight switches and LEDs. The LED next to each switch illuminates to indicate
that an operation controlled by that switch has been selected. Figure 17 shows a dual channel Audio Control LED/
Switch Module controlling the following functions:
ALL SPEAKERS EVAC
SELECTIVE EVAC
ALL SPEAKERS TALK
LOCAL SPEAKER ALERT
LOCAL SPEAKER EVAC.
The function of each switch is explained in the following paragraphs.
Figure 17
Audio Control LED/Switch Module for Dual Channel Operations
ALL SPEAKERS EVAC SWITCH
This switch is used to turn ON all of the speaker circuits on the EVAC channel, which will output the evacuation tone,
evacuation message, or a combination of both. Pushing the switch to the DOWN position cancels the tone/message
(if in progress), and turns OFF any active speaker circuits after the Evacuation tone/message is completed. The LED
(red) tracks the tone/message in progress.
SELECTIVE EVAC SWITCH
This switch is used to start the evacuation tone, evacuation message, or a combination of both on the evacuation
channel. As this switch is used when specific areas are to be evacuated, individual Speaker Select Switches must
be activated before turning this switch ON. Pushing this switch to the DOWN position will cancel the message, if in
progress, but will not turn OFF active speaker circuits. The LED (red) tracks the evacuation tone/message to indicate
when the tone/message is playing.
NOTE: The individual speaker circuits must be manually turned OFF as required.
DUAL CHANNEL
ALL SPEAKERS EVAC
SELECTIVE EVAC
ALL SPEAKERS TALK
(BLANK)
(BLANK)
(BLANK)
LOCAL SPEAKER ALERT
LOCAL SPEAKER EVAC
AUDIO CONTROL
SWITCH MODULE
ALL
SPEAKERS
EVAC
SELECTIVE
EVAC
ALL
SPEAKERS
TALK
LOCAL
SPEAKER
ALERT
LOCAL
SPEAKER
EVAC
DUAL CHANNEL
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000