RFC-1 Advanced Operation page 6.34
The previous example can be altered to print every day at 6:00 am. The programming is shown below.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0632 Date/time trigger 1: action sequence 6.6.4 0 11 Alarm block 1: block indicator
0633 Date/time trigger 1: month 6.6.4 0 15 Alarm block 1: alarm
0634 Date/time trigger 1: day - value 1 6.6.4 0 15 Alarm block 1: month
0635 Date/time trigger 1: day - value 2 6.6.4 0 15 Alarm block 1: day of week
0636 Date/time trigger 1: hour - value 1 6.6.4 0 0 Alarm block 1: start hour - V1
0637 Date/time trigger 1: hour - value 2 6.6.4 0 6 Alarm block 1: start hour - V2
0638 Date/time trigger 1: minute - value 1 6.6.4 0 0 Alarm block 1: end hour - V1
0639 Date/time trigger 1: minute - value 2 6.6.4 0 0 Alarm block 1: end hour - V2
Use multiple date/time triggers to repeat an event at different times. To print a second set of readings at 6:00 pm,
program another date/time trigger. Remember to use a 24-hour clock. The programming is shown below.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0624 Date/time trigger 2: action sequence 6.6.4 0 11 Alarm block 2: block indicator
0625 Date/time trigger 2: month 6.6.4 0 15 Alarm block 2: alarm
0626 Date/time trigger 2: day - value 1 6.6.4 0 15 Alarm block 2: month
0627 Date/time trigger 2: day - value 2 6.6.4 0 15 Alarm block 2: day of week
0628 Date/time trigger 2: hour - value 1 6.6.4 0 1 Alarm block 2: start hour - V1
0629 Date/time trigger 2: hour - value 2 6.6.4 0 8 Alarm block 2: start hour - V2
0630 Date/time trigger 2: minute - value 1 6.6.4 0 0 Alarm block 2: end hour - V1
0631 Date/time trigger 2: minute - value 2 6.6.4 0 0 Alarm block 2: end hour - V2
Or, use a single date/time trigger to repeat an event at an interval. To print a set of readings every 3 hours, program
a date/time trigger as shown below.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0632 Date/time trigger 1: action sequence 6.6.4 0 11 Alarm block 1: block indicator
0633 Date/time trigger 1: month 6.6.4 0 15 Alarm block 1: alarm
0634 Date/time trigger 1: day - value 1 6.6.4 0 15 Alarm block 1: month
0635 Date/time trigger 1: day - value 2 6.6.4 0 15 Alarm block 1: day of week
0636 Date/time trigger 1: hour - value 1 6.6.4 0 15 Alarm block 1: start hour - V1
0637 Date/time trigger 1: hour - value 2 6.6.4 0 3 Alarm block 1: start hour - V2
0638 Date/time trigger 1: minute - value 1 6.6.4 0 0 Alarm block 1: end hour - V1
0639 Date/time trigger 1: minute - value 2 6.6.4 0 0 Alarm block 1: end hour - V2
Obviously this is not an exhaustive list of the programming options but it should start to give you an idea of what is
possible using very little programming.

Table of Contents

Other manuals for Sine Systems RFC-1/B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sine Systems RFC-1/B and is the answer not in the manual?

Sine Systems RFC-1/B Specifications

General IconGeneral
BrandSine Systems
ModelRFC-1/B
CategoryRemote Control
LanguageEnglish

Related product manuals