RFC-1 Advanced Operation page 6.35
Suppose we need to turn a transmitter on every day at 5:30 am in April and that action sequence 3 is programmed to
perform this task. We will use date/time trigger 1 but any unused date/time trigger will work.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0632 Date/time trigger 1: action sequence 6.6.4 0 3 Alarm block 1: block indicator
0633 Date/time trigger 1: month 6.6.4 0 4 Alarm block 1: alarm
0634 Date/time trigger 1: day - value 1 6.6.4 0 15 Alarm block 1: month
0635 Date/time trigger 1: day - value 2 6.6.4 0 15 Alarm block 1: day of week
0636 Date/time trigger 1: hour - value 1 6.6.4 0 0 Alarm block 1: start hour - V1
0637 Date/time trigger 1: hour - value 2 6.6.4 0 5 Alarm block 1: start hour - V2
0638 Date/time trigger 1: minute - value 1 6.6.4 0 3 Alarm block 1: end hour - V1
0639 Date/time trigger 1: minute - value 2 6.6.4 0 0 Alarm block 1: end hour - V2
We can alter this example to turn the transmitter on only on weekdays, not on weekends, with the programming
change shown below.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0632 Date/time trigger 1: action sequence 6.6.4 0 3 Alarm block 1: block indicator
0633 Date/time trigger 1: month 6.6.4 0 4 Alarm block 1: alarm
0634 Date/time trigger 1: day - value 1 6.6.4 0 15 Alarm block 1: month
0635 Date/time trigger 1: day - value 2 6.6.4 0 13 Alarm block 1: day of week
0636 Date/time trigger 1: hour - value 1 6.6.4 0 0 Alarm block 1: start hour - V1
0637 Date/time trigger 1: hour - value 2 6.6.4 0 5 Alarm block 1: start hour - V2
0638 Date/time trigger 1: minute - value 1 6.6.4 0 3 Alarm block 1: end hour - V1
0639 Date/time trigger 1: minute - value 2 6.6.4 0 0 Alarm block 1: end hour - V2
Suppose we need to turn the transmitter off every day at 6:30 pm in April and that action sequence 4 is programmed
to perform this task. Date/time trigger 2 will trigger the action sequence. The programming is shown below.
- Programming -
Addr Description Section Default Current Alternate Use / Notes
0624 Date/time trigger 2: action sequence 6.6.4 0 4 Alarm block 2: block indicator
0625 Date/time trigger 2: month 6.6.4 0 4 Alarm block 2: alarm
0626 Date/time trigger 2: day - value 1 6.6.4 0 15 Alarm block 2: month
0627 Date/time trigger 2: day - value 2 6.6.4 0 15 Alarm block 2: day of week
0628 Date/time trigger 2: hour - value 1 6.6.4 0 1 Alarm block 2: start hour - V1
0629 Date/time trigger 2: hour - value 2 6.6.4 0 8 Alarm block 2: start hour - V2
0630 Date/time trigger 2: minute - value 1 6.6.4 0 3 Alarm block 2: end hour - V1
0631 Date/time trigger 2: minute - value 2 6.6.4 0 0 Alarm block 2: end hour - V2
Again, this is not an exhaustive list. But using the special trigger options it is easy to create recurring events without
a lot of programming.

Table of Contents

Other manuals for Sine Systems RFC-1/B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sine Systems RFC-1/B and is the answer not in the manual?

Sine Systems RFC-1/B Specifications

General IconGeneral
BrandSine Systems
ModelRFC-1/B
CategoryRemote Control
LanguageEnglish

Related product manuals