EasyManua.ls Logo

SMA SI 5048 - Operation in Conjunction with PV Inverters

SMA SI 5048
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Solar Technology AG Connecting External Sources
Technical Description SI5048-TEN093630 115
The "133.03 GnRmgTm" display value is used to display the remaining time of the generator meter.
Depending on the current request or the phase in which the generator state machine is, the following
times are displayed:
Remaining time of Run1h
Remaining run time during the warm up phase (Warm)
Remaining minimum run time in operation (Run)
Remaining run time during the power down time (Cool)
Remaining stop time after the power down time has expired (Lock)
Remaining time in the error state (Fail)
Remaining time in the locked error state (FailLock)
14.1.8 Operation in Conjunction with PV Inverters
If the battery is fully charged, the frequency limits the power output of the AC feed-in generators
(Sunny Boy). If the generator is now manually started, for example, the frequency would be lowered,
if required, as the Sunny Island synchronizes with the generator. The AC feed-in generators
(Sunny Boy) would then feed additional energy into the system and possibly overload the batteries.
In order to prevent this, in this case the stand-alone grid frequency is temporarily increased, in line with
the synchronization, until the AC feed-in generators (Sunny Boy) are disconnected from the stand-
alone grid as a result of the grid limits being exceeded.
NOTICE!
Wrong system design may lead to exceeding the maximal AC power of the
PV inverters.
The maximal AC output power of the PV inverters connected should not exceed
10 kW per Sunny Island.
Observe the following:
P
AC max
of the PV Inverter = 2 x P
AC nom
of the Sunny Island

Table of Contents

Related product manuals