Parameter lists SMA Solar Technology AG
170 SI5048-TEN093630 Technical Description
19.2.5 System Settings (250#)
Number Name Description Value Description Default
value
01 AutoStr Autostart
If the value 0 has been
set, this means that the
autostart is deactivated.
3
02 Dt Date in yyyy.mm.dd 99999999
03 Tm Time in hh:mm:ss 999999
04 BeepEna Button sound Off Disable On
On Enable
05 ClstCfg cluster configuration slave1 cluster slave 1 1Phase1
slave2 cluster slave 2
slave3 cluster slave 3
1Phase1 1 phase,
1 Sunny Island
1Phase2
1 phase,
2 Sunny Islands
1Phase3
1 phase,
3 Sunny Islands
3Phase
3 phase,
3 Sunny Islands
06 ComBaud Baudrate 1200 1200
4800
9600
19200
38400
57600
115K
09 ComAdr Address for
communication
10 SleepEna Sleep Mode Disable Enable Enable
Enable Disable
11 AfraEna Tertiary control (AFRA) Disable Enable Enable
Enable Disable
13 SlpAtNgt Switch off the slaves at
night
Disable Enable Disable
Enable Disable
14 SlpStrTm Start time for switching off
at night (sleep mode)
20:00:00
hh:mm:ss