Parameter lists SMA Solar Technology AG
152 SI5048-TEN093630 Technical Description
19.2.3 External Settings (230#)
231# Ext General
232# Grid Control
Number Name Description Value Description Default
value
03 ExtLkTm Lock time after reverse
power or relay
protection
0 min ...
60 min
20 min
06 ExtSrc External source PvOnly PV only PvOnly
Gen Generator
Grid Grid
GenGrid Generator / Grid
Number Name Description displayed
value
Description Default
value
01 GdVtgMin Minimum grid voltage 230 V / 50 Hz 184 V
220 V / 60 Hz 194 V
02 GdVtgMax Maximum grid
voltage
230 V / 50 Hz 264.5 V
220 V / 60 Hz 242 V
03 GdCurNom Gird nominal voltage 16 A
04 GdFrqNom Grid nominal
frequency
230 V / 50 Hz 50 Hz
220 V / 60 Hz 60 Hz
05 GdFrqMin Minimum grid
frequency
230 V / 50 Hz 47.5 Hz
220 V / 60 Hz 59.3 Hz
06 GdFrqMax Maximum grid
frequency
230 V / 50 Hz 50.2 Hz
220 V / 60 Hz 60.5 Hz
07 GdVldTm Minimum time
required for grid
(voltage and
frequency) to be
within permissible
range for connection
230 V / 50 Hz 30 sec
220 V / 60 Hz 300 sec
08 GdMod Grid interface GridCharge Charging on
the grid
GridCharge
GridFeed Charging and
feedback on
the grid