SMA Solar Technology AG Parameter lists
Technical Description SI5048-TEN093630 153
09 GdRvPwr Permissible grid
reverse power
(active power)
100 W
10 GdRvTm Permissible time for
grid reverse power
100 W
15 GdAlSns AI sensitivity Low low Normal
Medium Medium
Normal Normal
High high
37 GdVtgIncProEna Voltage rise
protection
Disable Enable Enable
Enable Disable
38 GdVtgIncPro Boundary for voltage
increase protection
230 V / 50 Hz 253 V
220 V / 60 Hz 242 V
40 Country Installation country
The installation land is
set based on the
corresponding
applicable norm.
The defaut value is set
according to your
order.
GER_VDE01
26_1_1
Germany
AS4777 USA
Other others
41 FedInMod Feeding into the grid
The value defines that
upon which the feed-
in is dependent.
Off off Off
Time Time
Signal digital signal
Com Communicatio
n
SignalCom
42 FeInSocStr SOC limit for grid
feeding start time
70 %
43 FedInSocStp SOC limit for grid
feeding stop time
60 %
44 FedInTmStr Start time for time-
dependent grid
feeding in hh:mm:ss
45 FedInTmStp Stop time for time-
dependent grid
feeding in hh:mm:ss
Number Name Description displayed
value
Description Default
value